Fire Resistance Design of Reinforced Concrete Structures

The design and construction of building structures must adhere to fire resistance performance requirements stipulated within the Building Regulations. When exposed to intense heat, concrete undergoes complex physical and chemical transformations.

Initially, the surface loses moisture, followed by spalling (explosive cracking) as internal moisture vaporizes. As temperatures rise further, the calcium silicate hydrates, the binding agents within the concrete, decompose, leading to a significant loss in strength and stiffness.

Steel reinforcement is also significantly affected by fire. Its tensile strength diminishes rapidly at elevated temperatures, increasing the risk of failure. Steel reinforcement suffers strength degradation with a 50% loss occurring around 560°C and a 75% loss at approximately 700°C. Therefore, adequate concrete cover is essential to delay the time it takes for the reinforcement to reach temperatures triggering structural failure.

concrete structure damaged by fire
Figure 1: Concrete structure damaged by fire

During a fire event, the primary structural concerns pertain to the floor construction directly above the flames and any supporting columns or walls. The fire resistance of the floor elements, comprising beams, ribs, and slabs, hinges critically on the thermal protection provided to the bottom reinforcement.

To ensure stability during a fire event, structural elements must exhibit a minimum specified period of fire resistance as determined by standardized testing procedures. The requisite fire resistance period depends on two primary factors:

  1. Building Purpose Group: The designated purpose group of the building, which categorizes its intended use and occupant occupancy levels, dictates the baseline fire resistance requirements.
  2. Building Height and Depth: Additionally, the height of the above-ground structure, or alternatively, the depth of a basement relative to the ground level, further influences the mandated fire resistance period. These correlations are detailed in Table 1.
Purpose group of buildingMinimum fire periods (hours) for elements of structure
Basement storyGround or upper story
Depth (m) of lowest basementHeight (m) of top floor above ground in building or separated part of a building
≤ 10>10≤ 5≤ 18≤ 30>30
Residential Flats and maisonettes  1.0  1.50.51.01.52.0
Residential dwelling houses0.50.51.0
Residential (institutional)1.01.50.51.01.52.0
Other residential1.01.50.51.01.52.0
Office (not sprinklered)1.01.50.51.01.5
Office (sprinklered)1.01.00.51.01.02.0
Shop and commercial (not sprinklered)1.01.51.01.01.5
Shop and commercial (sprinklered)1.01.00.51.01.02.0
Assembly and recreation (not sprinklered)1.01.51.01.01.5
Assembly and recreation (sprinklered)1.01.00.51.01.02.0
Industrial (not sprinklered)1.52.01.01.52.0
Industrial (sprinklered)1.01.50.51.01.52.0
Storage and other non-residential (not sprinklered)1.52.01.01.52.0
Storage and other non-residential (sprinklered)1.01.50.51.01.52.0
Table 1: Building regulations (minimum fire periods)

Beyond the minimum regulatory requirements, building insurers may impose stricter fire resistance demands for specific scenarios, such as high-value storage facilities, where contents and potential reconstruction costs necessitate extended fire containment.

Fire Resistance Design Approaches in BS 8110

British Standard 8110 (BS 8110) establishes a two-tier framework for fire resistance design:

  • Part 1: Simple Recommendations: This section caters to a broad range of applications and provides straightforward recommendations suitable for most common design scenarios.
  • Part 2: Detailed Design Methods: For intricate fire resistance considerations, Part 2 offers a more nuanced approach, presenting three distinct design methods:
    • Tabulated Data: Predefined tables specify minimum element dimensions and concrete cover thicknesses for various structural members, simplifying selection for typical cases.
    • Furnace Testing: Direct fire exposure testing on specific structural components can be conducted to validate or optimize their fire resistance performance.
    • Fire Engineering Calculations: Advanced fire engineering analysis methods enable bespoke calculations of component and system behaviour under fire conditions, offering greater flexibility and design customization for complex scenarios.

Importantly, BS 8110 recognizes the influence of section geometry on concrete cover requirements. For beams and ribs, the specified cover thicknesses can be adjusted based on the actual width of the structural member, optimizing material usage and maintaining adequate protection for the embedded reinforcement.

Part 1 of the relevant design standard adopts the same fundamental data as Part 2 for determining fire resistance requirements. However, the presentation format differs in two key aspects:

  1. Nominal Cover: Instead of tailoring cover thicknesses based on section width, Part 1 specifies a single “nominal cover” value applicable to all reinforcement, inclusive of an allowance for link elements in beams and columns.
  2. Simplified Values: Unlike Part 2’s dynamic adjustments based on section geometry, Part 1 utilizes fixed cover and dimension values tabulated in Tables 2 and 3 for simplified application in diverse design scenarios.
Fire period (hours)Nominal cover (mm)
BeamsFloorsRibsColumns
Simply supportedContinuousSimply supportedContinuousSimply supportedContinuous 
0.520202020202020
1.020202020202020
1.520202520352020
2.040303525(45)3525
3.0(60)40(45)35(55)4025
4.0(70)(50)(55)(45)(65)(50)25
Table 2: Nominal cover for different fire periods (BS 8110)

Where values are shown in parenthesis, additional measures should be taken to reduce the risk of spalling. For the purpose of assessing a nominal cover for beams and columns, an allowance for links of 10mm has been made to cover the range from 8 mm to 12 mm.

Minimum beam dimensions for fire resistance
Figure 2: Minimum beam dimensions for fire resistance
minimum dimensions for floors fire resistance
Figure 3: Minimum floor dimensions for fire resistance
Minimum column dimensions for fire resistance
Figure 4: Minimum column dimensions for fire resistance
Fire resistance period (hours)Minimum beam width (b) mmMinimum rib width (b) mmMinimum floor thickness (h) mmMinimum column width (b)Minimum wall thickness for reinforcement percentage p
Fully exposed (mm)50% exposed (mm)One face exposed (mm)p < 0.4 (mm)0.4 < p < 1.0 (mm)p > 1.0 (mm)
0.52001257515012510015010075
1.02001259520016012015012075
1.5200125110250200140175140100
2.0200125125300200160160100
3.0240150150400300200200150
4.0280175170450350240240180
Table 3: Minimum dimensions of structural elements

The design approach considers the different implications of fire on load-bearing behaviour:

  • Simply Supported Spans: For these elements, a 50% strength loss in the bottom reinforcement can be critical, necessitating stricter cover requirements to ensure continued stability.
  • Continuous Spans: In this case, some degree of bottom reinforcement strength loss can be tolerated as the top reinforcement retains its full capacity and contributes to load redistribution.

Excessive concrete cover, while enhancing thermal protection, also carries the risk of premature spalling during fire exposure. This phenomenon is particularly concerning for concretes containing aggregates rich in silica. Therefore, finding the optimal balance between adequate cover and minimizing spalling risk becomes crucial for effective fire resistance design.

When exceeding a nominal concrete cover of 40 mm, alternative strategies necessitate consideration. BS 8110 Part 2 details several potential approaches. Primarily, cover reduction is preferred, achieved through supplementary protection elements like applied finishes, false ceilings, or lightweight aggregates (LWA). A final option involves deploying “sacrificial steel,” exceeding necessary reinforcement to accommodate potential fire-induced strength loss.

If exceeding 40 mm remains unavoidable, additional reinforcement via welded steel fabric embedded 20 mm from the concrete surface is permitted. However, significant practical limitations exist, and potential conflict with durability requirements in certain scenarios must be assessed.

Fire Resistance Design Approaches in EN 1992 (Eurocode 2)

The general requirement in Eurocode 2 for the fire design of reinforced concrete structures is that structures should be able to retain their load-bearing function during the required time of fire exposure. Eurocode 2, Part 1-2: Structural fire design, offers three approaches for fire resistance determination: advanced, simplified, and tabular methods.

While tabular methods provide the fastest route for calculating minimum slab dimensions and cover thicknesses, their application is subject to specific limitations. Consulting specialist literature is recommended for further guidance on the intricacies of advanced and simplified methods.

Unlike the other approaches, the tabular method employs the concept of nominal axis distance (a) instead of a minimum cover. This parameter represents the distance from the centre of the primary reinforcing bar to the member’s exposed surface. It is important to note that the value of a is nominal, not a true minimum requirement.

EC 2 also introduces a more adaptable approach to fire safety design, founded on the concept of “load ratio” – the ratio of applied load at the fire limit state to the element’s ambient temperature capacity.

Fire Performance Criteria

Three fundamental performance criteria are established:

  • Criterion R: Load bearing function is maintained for the requisite fire resistance duration.
  • Criterion I: Average temperature rise across the unexposed surface does not exceed 140 K, and no point on that surface surpasses 180 K, thereby potentially preventing ignition of combustible materials on the protected side of a compartment wall.
  • Criterion E: No cracks, holes, or openings allowing flame or hot gas passage from the fire compartment to adjacent unburnt compartments.

For standard fire exposure, members must comply with criteria R, E, and I as follows:

  • Load bearing only: Mechanical resistance (criterion R)
  • Separation only: Integrity (criterion E) and, optionally, insulation (criterion I)
  • Combined load bearing and separation: Criteria R, E, and, optionally, I

Notations like R30, R60, E30, E60, I30, and I60 signify compliance with the respective criteria (R, E, and I) during at least 30 or 60 minutes of standard fire exposure. REI 90 signifies simultaneous compliance with all three criteria for at least 90 minutes, with the most critical criterion governing the classification.

These criteria are evaluated within a structural fire design analysis encompassing the following steps:

  1. Selection of relevant fire scenarios based on a fire risk assessment.
  2. Determination of the corresponding design fire, applicable to only one fire compartment at a time.
  3. Calculation of temperature evolution within structural members, considering fire exposure through facade and roof openings for external members.
  4. Calculation of the mechanical behaviour of the structure under fire exposure.

Design Based on Tabulated Data

Tabulated data presents minimum cross-sectional dimensions and nominal axis distances for primary reinforcement, accompanied by detailed specifications tailored to each member type. This method offers a validated approach for verifying the fire resistance of individual structural members, providing recognized design solutions for standard fire exposures up to a duration of 240 minutes. A key advantage is the expedited verification of whether dimensions derived from ambient temperature design remain acceptable under fire conditions. The following considerations are pertinent:

  • The tabulated values are predicated upon a standard fire exposure as defined by ISO 834.
  • Their development rests upon empirical tests, further corroborated by practical experience and theoretical evaluations of test results. The values themselves err on the side of conservatism to ensure safety margins.
  • Applicability is limited to normal-weight concrete composed of siliceous aggregates. In beams and slabs utilizing calcareous or lightweight aggregates, a 10% reduction in minimum cross-sectional dimensions is permissible.
  • Adhering to tabulated values eliminates the necessity for additional assessments regarding explosive spalling, shear and torsion capacity, and anchorage details.
image 12
Figure 5: Sections through structural members, showing nominal axis distance a (Source EN 1992-1-2:2004)

General rules

1. To ensure compliance with criterion R (load-bearing function) during the specified standard fire resistance, minimum requirements for cross-sectional dimensions and reinforcement axis distances have been established. The tabulated data assume a reference load level of μfi = 0.7.

2. The tables specify minimum concrete cover as the distance “a” between the main reinforcement’s axis and the nearest concrete surface (see Figure 5). These axis distances are nominal values, not requiring tolerance allowances. Note that Eurocode 2, Part 1-1, addressing normal temperature design, defines concrete cover “c” as the distance from the reinforcing bar’s edge to the closest concrete surface. Therefore, for a longitudinal rebar with a diameter φbar, the relationship between “a” and “c” can typically be expressed as a = c + φstirrup + φbar/2, where φstirrup represents the stirrup diameter.

3. Minimum axis distances for reinforcement located within tensile zones of simply supported beams and slabs were calculated using a critical steel temperature (θcr) of 500 °C. This critical temperature signifies the point at which steel yields under the fire-induced steel stress (σs,fi). For prestressing tendons, critical temperatures are assumed to be 400 °C for bars and 350 °C for strands and wires.

Fire Resistance Requirements of Slabs (EC2)

In ensuring acceptable fire resistance for reinforced and prestressed concrete slabs, Table 4 provides minimum thicknesses that satisfy the separation function (Criteria E and I). While thicker floor finishes can enhance separation, load-bearing capacity (Criterion R) can be solely determined by the slab thickness required for design under EN 1992-1-1 if this function is the only concern. This approach streamlines assessment by considering separate functions when necessary and leveraging existing design rules for load-bearing capacity.

image 15
Figure 6: Concrete slab with floor finishes (Source EN 1992-1-2:2004)

Simply supported solid slabs

Table 4 provides minimum values of axis distance to the soffit of simply supported slabs for standard fire resistances of R 30 to R 240. In two-way spanning slabs, a denotes the axis distance of the reinforcement in the lower layer.

Standard Fire ResistanceMinimum dimensions (mm)
Slab thickness hs (mm)Axis distance a
One wayTwo-way ly/lx ≤ 2.0Two way ly/lx ≤ 2.0
12345
REI 306010*10*10*
REI 60802010*15*
REI 901003015*20
REI 120120402025
REI 180150553040
REI 240175654050
ly and lx are the spans of a two-way slab (two directions at right angles) where ly is the longer span. For prestressed slabs, the increase of axis distance according to 5.2(5) should be noted.
The axis distance (a) in Columns 4 and 5 for two-way slabs relates to slabs supported at all four edges. Otherwise, they should be treated as a one-way spanning slab.
* Normally the cover required by EN 1992-1-1 will control.
Table 4: Minimum dimensions and axis distances for reinforced and prestressed concrete simply supported one-way and two-way solid slabs (Source EN 1992-1-2:2004)

The values given in Table 4 (Columns 2 and 4) also apply to one-way or two-way continuous slabs.

Ribbed Slabs

Assessing the fire resistance of ribbed slabs, reinforced or prestressed, follows different paths for one-way and two-way configurations. For one-way slabs, specific provisions for beams, Table 4, columns 2 and 5 for flanges govern.

In contrast, two-way ribbed slabs rely on the values in Tables 5 and 6, alongside additional rules, assuming predominantly uniform loading. These tables cater to simply supported or restrained edge scenarios with varying fire resistance requirements and reinforcement detailing stipulations.

Notably, Table 5 applies to simply supported or one restrained edge cases with fire resistance below REI 180 where specific upper reinforcement arrangements are absent. For slabs with at least one restrained edge, Table 6 takes precedence, and section 5.6.3(3) of EN 1992-1-2 dictates the upper reinforcement detailing across all fire resistance levels.

Standard fire resistanceMinimum dimensions (mm)
Possible combinations of widths of ribs bmin and axis distance aSlab thickness hs and axis distance a in flange
12345
REI 30bmin = 80
a = 15*
  hs = 80
a = 10*
REI 60bmin = 100
a = 35
120
25
≥200
15*
hs = 80
a = 10*
REI 90bmin = 120
a = 45
160
40
≥250
30
hs = 100
a = 15*
REI 120bmin = 160
a = 45
190
55
≥300
40
hs = 120
a = 20
REI 180bmin = 220
a = 75
260
70
≥410
60
hs = 150
a = 30
REI 240bmin = 280
a = 90
350
75
≥500
70
hs = 175
a = 40
asd = a + 10
asd denotes the distance measured between the axis of reinforcement and lateral surface of the rib exposed to fire.
*Normally the cover required by EN 1992-1-1 will control
Table 5: Minimum dimensions and axis distances for two-way spanning ribbed slabs (waffle slabs) in reinforced concrete with simply supported edges (Source EN 1992-1-2:2004)
Standard fire resistanceMinimum dimensions (mm)
Possible combinations of widths of ribs bmin and axis distance aSlab thickness hs and axis distance a in flange
12345
REI 30bmin = 80
a = 10*
  hs = 80
a = 10*
REI 60bmin = 100
a = 25
120
15*
≥200
10*
hs = 80
a = 10*
REI 90bmin = 120
a = 35
160
25
≥250
15*
hs = 100
a = 15
REI 120bmin = 160
a = 45
190
40
≥300
30
hs = 120
a = 20
REI 180bmin = 310
a = 60
600
50
 hs = 150
a = 30
REI 240bmin = 450
a = 70
700
60
 hs = 175
a = 40
asd = a + 10
asd denotes the distance measured between the axis of reinforcement and lateral surface of the rib exposed to fire.
*Normally the cover required by EN 1992-1-1 will control
Table 6: Minimum dimensions and axis distances for two-way spanning ribbed slabs (waffle slabs) in reinforced concrete with at least one restrained edge (Source EN 1992-1-2:2004)

Flat Slabs

Flat slabs exhibiting minimal moment redistribution (less than 15% in accordance with EN 1992-1-1, Section 5) may be assessed for fire resistance utilizing the same principles as one-way slabs, employing axis distances and minimum thicknesses outlined in Table 7. However, for fire resistance ratings of REI 90 or higher, additional measures are mandated.

At least 20% of the top reinforcement spanning intermediate supports, as prescribed by EN 1992-1-1, must be continuous across the entire slab and positioned within the column strip. Furthermore, no reduction in the minimum slab thickness, regardless of floor finishes, is permitted. In essence, elevated fire resistance demands necessitate stricter continuity and thickness requirements for flat slabs with limited moment redistribution.

Standard fire resistance  Minimum dimensions (mm)
Slab thickness hsAxis distance a
123
REI 3015010*
REI 6018015*
REI 9020025
REI 12020035
REI 18020045
REI 24020050
*Normally the cover required by EN 1992-1-1 will control
Table 7: Minimum dimensions and axis distances for reinforced and prestressed concrete solid flat slabs (Source EN 1992-1-2:2004)

Fire Resistance Requirement of Beams

The fire resistance of reinforced and prestressed concrete beams can be confidently assessed using the data presented in Tables 8 and 9. These tables apply specifically to beams experiencing fire exposure on three sides, assuming the top surface is adequately insulated by overlying slabs or other elements throughout the designated fire resistance period. For scenarios where fire exposure occurs on all sides of the beam, additional considerations outlined in clause 4.6.5 of EN 1992 1-2 must be taken into account.

image 16
Figure 7: Definition of dimensions for different types of beam section (Source EN 1992-1-2:2004)

Simply supported beams

Table 8 provides minimum values of axis distance to the soffit and sides of simply supported beams together with minimum values of the width of beam, for standard fire resistances of R 30 to R 240.

Standard fire resistanceMinimum dimensions (mm)
Possible combinations of a and bmin where a is the average axis distance and bmin is the width of the beamWeb thickness bw
Class WAClass WBClass WC
12345678
R30bmin = 80
a = 25
120
20
160
15*
200
15*
808080
R60bmin = 120
a = 40
160
35
200
30
300
25
10080100
R90bmin = 150
a = 55
200
45
300
40
400
35
110100100
R120bmin = 200
a = 65
240
60
300
55
500
50
130120120
R180bmin = 240
a = 80
300
70
400
65
600
60
150150140
R240bmin = 280
a = 90
350
80
500
75
700
70
170170160
asd = a + 10
asd is the axis distance to the side of beam for the corner bars (or tendon or wire) of beams with only one layer of reinforcement. For values of bmin greater than that given in Column 4 no increase of asd is required.
* Normally the cover required by EN 1992-1-1 will control.
Table 8: Minimum dimensions and axis distances for simply supported beams made with reinforced and prestressed concrete (Source EN 1992-1-2:2004)

Continuous Beams

For continuous beams with standard fire resistance ratings ranging from R 30 to R 240, Table 9 specifies minimum axis distances to the soffit and sides, along with minimum beam widths. However, the validity of this data hinges on two crucial conditions:

  1. Detailed Design Compliance: All prescribed detailing rules outlined in the source material must be meticulously followed.
  2. Moment Redistribution Limit: The redistribution of bending moments at normal temperatures must not exceed 15%. Beyond this threshold, the beams must be treated as simply supported for fire resistance assessment purposes.
Standard fire resistanceMinimum dimensions (mm)
Possible combinations of a and bmin where a is the average axis distance and bmin is the width of the beamWeb thickness bw
Class WAClass WBClass WC
12345678
R30bmin = 80
a = 15*
160
12*
  808080
R60bmin = 120
a = 25
200
12*
  10080100
R90bmin = 150
a = 35
250
25
  110100100
R120bmin = 200
a = 45
300
35
450
35
500
30
130120120
R180bmin = 240
a = 60
400
50
500
50
600
40
150150140
R240bmin = 280
a = 75
500
60
650
60
700
50
170170160
asd = a + 10
asd is the axis distance to the side of beam for the corner bars (or tendon or wire) of beams with only one layer of reinforcement. For values of bmin greater than that given in Column 4 no increase of asd is required.
* Normally the cover required by EN 1992-1-1 will control.
Table 9: Minimum dimensions and axis distances for continuous beams made with reinforced and prestressed concrete (see also Table 8) (Source EN 1992-1-2:2004)

Fire Resistance Requirement of Columns

The fire resistance of reinforced and prestressed concrete columns in braced structures primarily subjected to compression can be evaluated through two methods (Method A and Method B). Method A offers a streamlined approach, relying on the data in Table 10 and adhering to specific accompanying rules. This method ensures adequate fire resistance under these conditions, enabling efficient structural design in fire-resistant buildings.

  • effective length of the column (for definition see EN 1992-1-1 Section 5) under fire conditions: lO,fi ≤ 3 m
  • first-order eccentricity under fire conditions: e = MOEd,fi / NOEd,fi ≤ emax
  • amount of reinforcement: As < 0.04 Ac

Degree of utilization in the fire situation, μfi, has been introduced in Table 10. This accounts for the load combinations, compressive strength of the column and bending including second-order effects.

μfi = NEd.fi/NRd

where;
NEd,fi is the design axial load in the fire situation,
NRd is the design resistance of the column at normal temperature conditions

NRd is calculated according to EN 1992-1-1 with Ym for normal temperature design, including second-order effects and an initial eccentricity equal to the eccentricity of NEd,fi.

Standard fire resistanceMinimum dimensions (mm)
Column width bmin/axis distance a of the main bars
Exposed on more than one sideExposed on one side
μfi = 0.2μfi = 0.5μfi = 0.7μfi = 0.7
12345
R 30200/25200/25200/32
300/27
155/25
R 60200/25200/36
300/31
250/46
350/40
155/25
R 90200/31
300/25
300/45
400/38
350/53
450/40**
155/25
R 120250/40
350/35
350/45**
450/40**
350/57**
450/51**
175/35
R 180350/45**350/63**450/70**230/55
R 240350/61**450/75**295/70
** Minimum 8 bars
Table 10: Minimum column dimensions and axis distances for columns with rectangular or circular section (Source EN 1992-1-2:2004)

Fire Resistance Requirements of Load Bearing Walls

Adequate fire resistance of load-bearing reinforced concrete walls may be assumed if the data given in Table 11 and the following rules are applied. The minimum wall thickness values given in Table 11 may also be used for plain concrete walls (see EN 1992-1-1, Section 12).

Standard Fire ResistanceMinimum dimensions (mm)
μfi = 0.35μfi = 0.7
Wall exposed on one sideWall exposed on two sidesWall exposed on one sideWall exposed on two sides
12345
REI 30100/10*120/10*120/10*120/10*
REI 60110/10*120/10*130/10*140/10*
REI 90120/20*140/10*140/25170/25
REI 120150/25*160/25160/35220/35
REI 180180/40200/45210/50270/55
REI 240230/55250/55270/60350/60
* Normally the cover required by EN 1992-1-1 will control.
Table 11: Minimum dimensions and axis distances for load – bearing concrete walls (Source EN 1992-1-2:2004)

Conclusion

Designing for fire resistance in reinforced concrete structures requires a delicate balance between minimizing material usage and ensuring adequate structural integrity during a fire event. This can be achieved by utilizing minimum concrete covers and dimensions prescribed in codes and guidelines like Eurocode 2 part 2.

These minimums safeguard the internal reinforcement from excessive temperature rise, protecting its strength and maintaining load-bearing capacity. However, blindly applying these minimums is insufficient. Fire resistance design also involves factors like:

  • Member type and loading: Different elements, like beams, columns, and slabs, experience varying heat transfer and stress under fire. Specific rules tailored to each element dictate minimum covers and dimensions to ensure stability.
  • Fire exposure conditions: The duration and intensity of the fire exposure significantly impact required member sizes and cover thicknesses.
  • Concrete properties: High-strength concrete offers improved fire resistance compared to normal-strength concrete, allowing for potentially thinner sections due to its enhanced thermal insulation.

Optimizing fire resistance design with minimum covers and dimensions necessitates a holistic approach, considering element type, exposure conditions, and material properties. By applying code provisions and understanding the underlying thermal and structural behaviour, engineers can create fire-resistant concrete structures while minimizing material consumption and cost.

LEAVE A REPLY

Please enter your comment!
Please enter your name here