8.7 C
New York
Saturday, September 21, 2024
Home Blog Page 54

Design of Ground Beams Using Staad Pro

Ground beams are employed in reinforced concrete substructures for a lot of reasons. They can be differentiated from plinth beams due to a slight variation in the purpose of their construction. Plinth beams are used to connect (chain) separate pad bases together, and blockwork can be built off the plinth beams. On the other hand, ground beams are designed mainly for the purpose of receiving load from the ground floor slab or raft, alongside other functions as envisaged by the designer.

In the design of beam and raft foundation, ground beams receive ground floor/raft slab pressure loads. These loads could be from earth pressure reactions or occupancy loads/dead loads.

Let us consider two cases as shown below:

Case 1: Raft Slab on Ground Beam Foundation

GROUND%2BBEAM
Fig 1: A typical section of a ground beam supporting a raft foundation

In this case, as shown in Fig 1, a raft foundation supported on ground beams is used to overcome the low bearing capacity of the soil. This is the cheapest alternative for constructing foundations on weak soils carrying relatively low/moderate superstructure load. The advantages of this method are;

(1) The volume of excavation to be done is reduced to a minimum since excavation will be done for the ground beams only
(2) It is relatively easy to construct
(3) The slab performs the triple function of acting as a structural raft slab, ground floor slab (oversite concrete), and damp proof course.

However, this construction method can demand beams that are slightly deeper than normal in order to raise the ground floor to a height above the compound level.

This type of foundation can be analysed and designed and using finite element analysis or rigid theory. When using the rigid theory, the arrangement of the foundation and the loadings have to be fairly symmetrical, and the footing will have to be stiff enough in order to assume full rigidity. Furthermore, we usually assume that the stiffness of the raft slab covers the weak patches of the soil adequately.

The implication of the rigid theory in design is that the settlement of the soil will even out under the rigid footing, with high internal forces developing in the slab. When a flexible approach is used, there would be a differential settlement, but lower stresses on the elements, thereby leading to a more economical design. Note that rigidity criteria are a function of superstructure stiffness and soil stiffness. Different codes of practice have their own definition of rigidity.

In the rigid method, usually, the soil pressure on the slab is evaluated, and transferred to the beams by assuming a sort of combined footing approach.

Case 2: Ground Floor Slab on Ground Beam 

2222
Fig 2: Ground beams on pile caps

In this approach as shown in Figure 2, the ground floor slabs are supported directly by ground beams, which in turn are supported by pile caps. In this case, the slabs are designed as suspended slabs, and ground pressure reactions are not taken into account.

Worked Example

Let us assume that you have a raft foundation on ground beams to design, and you have been able to obtain the soil pressure. Note that the variation of soil pressure is usually a function of location and the applied loading. See an example of how to determine it below;

Structural Design of Flat Raft Foundation (Rigid Approach)

Let us assume that in the example above, we will be introducing ground beams (1200mm x 225mm) along the column axes as shown in Figure 3. Let the thickness of the slab be 200 mm.

Design%2Bof%2Braft%2Bfoundation
Fig 3: Sketch of how ground beams were introduced in the model

From the analysis, the maximum pressure on the raft slab was discovered to be 49.975 kN/m2. Note that with the introduction of the ground beams, the 1000 mm projection is no longer necessary. So a simplified way of analysing and designing the ground beams using Staad Pro is as follows.

Step 1: Model the ground beam as appropriate and support it with pinned support at the column points. Also, assign the properties of the beam (1200 mm x 225 mm).

st%2Bmodel
Fig 4: Modelling of the ground beams on Staad Pro

Step 2: Create/add a ‘floor load’ and assign it to the beams as shown below. This uses the tributary area method to transfer the load to the beams;

FLOOR%2BLOAD
Fig 5: Application of ground pressure load

Remember that the load is assigned a positive value because it is an upward pressure.

Step 3: Run the analysis to obtain the bending moment given below.

Internal%2Bstresses%2Bdiagram

Let us consider the beam along grid line B.

BENDING%2BMOMENT%2BDIAGRAM%2BGROUND%2BBEAM
Bending Moment Diagram
SFD
Shear Force Diagram

The result from Staad Pro software indicates that the maximum span moment is 463 kNm. With this, you can provide the reinforcements at ULS depending on the code of practice you are using. Note that where applicable, you might need to consider wall loads, self-weight, etc, but note that these gravity forces will be likely beneficial because they will reduce the resultant load on the beam due to earth pressure. This is just a simple and straightforward approach that would always yield conservative results.

Thank you for visiting Structville today, and God bless you.


Different Methods of Staircase Modelling, Analysis, and Design

Staircases provide simple solutions for vertical circulation in a building. In this article, we will present the different methods of modelling a simple reinforced concrete staircase for the purpose of analysis and structural design.

The different methods considered in this article are as follows;

(1) Modelling the staircase using finite element plates
(2) Modelling the staircase as a simple 2D frame
(3) Modelling the staircase as a linear simply supported beam

The aim of this post is to compare the results obtained from the different modelling alternatives and give reinforced concrete designers a little idea about the results to expect from their assumptions.

Let us consider a section of a staircase with dimensions as shown below;

12345
Fig 2: Section of Staircase

The loading on the staircase is as follows;

Ultimate load on the flight = 15.719 kN/m2
Ultimate load on the landing = 14.370 kN/m2
Width of staircase = 1000 mm

We are going to model and analyse the staircase section shown using the three different methods described above.

Finite Element Plate Model (Staad Pro)

In this approach, the full dimensions and geometry of the staircase will be modelled using finite element plates. The thickness of the waist of the staircase will be assigned as the thickness of the plates, while the rise and threads will be ignored. The size of the finite element plates can be chosen to be square or rectangular but is preferable to keep the model uniform.

The 3D model of the staircase is given below;

rendered%2B3d
Fig 3: Rendered 3D Model of the Staircase

To consider the effect of the support condition on the behaviour of the staircase, it will be modelled as pinned-pinned condition and pinned-roller support condition.

Pinned-pinned supports

file%2Bview
Fig 4: Model of the staircase with pinned-pinned support

The static analysis of the structure gave the result below;

MX
Fig 5: Transverse Bending Moment on the Staircase (Mx)
MY
Fig 6: Longitudinal Bending Moment (My) on the Staircase

Pinned-roller support

pinned roller
Fig 7: Modelling the Staircase with Pinned-Roller Support

The analysis result gave the following;

Fig 8: Transverse Bending Moment (Mx)
rp%2Bmy
Fig 9: Longitudinal Bending Moment (My)

Static 2D Frame Model

In this case, the geometry of the staircase (height, landing, and angle of flight) is modelled as line elements and analysed as a 2D frame subjected to static load. The typical model is shown below.

Pinned-Pinned Support

2d

The result is as given below;

simple%2Bbeam
Fig 10: Bending moment on the Staircase (Frame Model; pinned-pinned support)

Pinned-Roller Support

pinned roller%2Bbeam
Fig 11: Bending Moment on the staircase (pinned-roller model)

Simply Supported Beam Model

In this case, the entire geometry of the staircase is idealised and analysed as a simply supported linear beam model as shown below.

manual
Figure 12: Bending Moment on the stair (simply supported beam model – horizontal length)

Discussion of Results

  1. The analysis results using the above-named methods gave all the bending moments in the staircase to be sagging.
  2. The finite element plate model gave the maximum sagging at the flight to be 41.1 kNm (see Fig 5), while the maximum sagging moment on the landing was found to be 32.6 kNm (see Fig 6). This result was found in both the pinned-pinned and pinned-roller model, therefore, there is no difference in using any of the support conditions in Staad Pro.
  3. The static 2D frame model of the staircase gave the maximum sagging moment on the flight to be 41.1 kNm, while the maximum sagging moment on the flight was 33.82 kNm (see Fig 10 and 11). In principle, it can be said there is no difference in modelling the staircase as a simple 2D frame or as a 3D plate model. The former is quicker and less complicated.
  4. The model of span dimension adopted for the manual equivalent beam calculation was picked from SCALE software, and the maximum moment on the flight was found to be 36.04 kNm (see Fig 12). This is about 12.3% less than other models. A little consideration will show that this effect stems from the span dimensions.

To take care of this, let us modify the flight dimensions as follows;
Lf,m = Lf/cos ϕ
Where Lf is the horizontal span of flight,  Lf,m is the actual length of the flight, and ϕ is the angle of inclination of the flight.

Thus; Lf,m = 1.75m/cos 34.4 = 2.12m

This gave the result below;

modified
Fig 13: Bending moment on the stair (simply supported beam model, developed length)

We can see that is more comparable and conservative when compared with results from computer models. Therefore, for all simple staircases, we can use the developed length of the flight instead of the horizontal length to analyse the staircase as a simply supported beam. However, when checking for deflection, we should use the horizontal length.

Thank you for visiting Structville today. God bless.


Deflection of Elastic Systems Using Castigliano’s Theorem

Castigliano’s method for calculating deflections is an application of his second theorem, which states that if the strain energy of a linearly elastic structure can be expressed as a function of generalised force Pi then the partial derivative of the strain energy with respect to generalised force gives the generalised displacement wi in the direction of Pi.

The second theorem of Castigliano is applicable to linearly elastic (Hookean material) structures with constant temperature and unyielding supports.

In general, this is given by;

wi = ∂U/∂Pi

The strain energy stored in a linear elastic system due to bending is given by;

strain%2Benergy

Solved Example
For the frame loaded as shown below, let us find the vertical deflection at point C due to bending using Castigliano’s theorem.

FRAME

Solution
Section BC
Mx = -20x

U1 = ∫[(-20x)2/2EI] dx  =  ∫ -400x2/2EI = -400x3/6EI
Knowing that the limit x = 1.5m;
U1 = 225/EI

Section AB
My = (-20 × 1.5m) = 30 kNm

U2 = ∫[(-30)2/2EI] dy  =  ∫ -900/2EI = -900y/2EI
Knowing that the limit y = 2.5m;
U2 = 1125/EI

Total strain energy = U1 + U2 = (225/EI) + (1125/EI) = 1350/EI

Let the vertical deflection at point C be δv

Work done by the externally applied load = 1/2(P × δ)
Work done = Strain energy stored in the system

1/2(20 × δ) = 1350/EI

δv = 135/EI metres

Structville Design Challenge Results (1st Edition)

result

On 14th of May, 2018, Structville Integrated Services announced the commencement of Structville Design Challenge for civil engineering students in Nigeria. (If you missed it, you can read post HERE). By the special grace of God, the competition has come and gone, and I wish to appreciate everyone who participated in the exercise.


The price money goes as follows;
1st position – NGN 10,000
2nd position – NGN 3,000
3rd position – NGN 2,000

Competition Details
Total number of successful applicants = 20
Total number of scripts submitted by dead line = 14
Total number of accepted scripts = 12
Total number of assessed scripts = 12

Rationale
Human capacity building in Nigeria has become a necessity, and we must all wake up to that fact. The motivation to start up something is one thing, but staying motivated to finish it up is another thing. The main aim of this competition was to steer the younger generation to a path of creativity, curiosity, technical capacity, problem solving, and tenacity. It was also designed to make them optimistic and look forward to a wonderful career in structural engineering.

While assessing the scripts, I made a lot of observations, and I will briefly summarise them using the points below;

GROUND%2BFLOOR%2BPLAN

FIRST%2BFLOOR%2BPLAN

(1) A lot of participants disregarded the first instruction of the exercise which was to pay attention to details. A lot of people lost marks by assuming weight of finishes, when the details of the finishes were clearly specified. Other people quoted values and formulars without properly referencing them. This affected a lot of people.

(2) In most cases, there was poor reading and interpretation of the architectural drawing. All those who modified the structure significantly lost a lot of marks.  However, I saw a lot of brilliance in some people with the way they managed the complexities of the architectural drawing, and produced a very good design. Some others came up with interesting GA’s that are stable and buildable, but not very economical, so they lost marks in that aspect. For some others, they came up with GA’s that are good, but did not reflect it properly in their analysis.

(3) No single person from South-East or South-South part of Nigeria participated in the exercise. I hope to see more of them next time.

(4) Finally, structural design is not about evaluating  M/fcubd2 and providing 2Y16, but it is more about the processes that led to the result, and the ability to execute the design economically, with adequate reliability.

So this is the result of the challenge;

RESULT%2BSHEET

I wish to say a very big congratulations to the winners;

1st PositionUSMAN UMAR (Ahmadu Bello University, Zaria)
2nd PositionOgungbire Adedolapo (Osun State University, Osogbo)
3rd PositionOlajide Bukoye (Federal Polytechnic Offa, Kwara State)

We will be celebrating them with their certificates and prize money in our next post. Structville will engage all the participants with corrections, recommendations, and discussion on all aspects of the design. Thank you, and God bless you.


Design of Precast Seating Decks for Stadium

One of the most common concepts for the construction of sports stadiums today involves having precast concrete terrace units (seating decks) spanning between raker beams while at the same time, resting on each other. The successive arrangement of these precast seating units on the raker beams forms the grandstand of the stadium. The raker beams are usually formed in-situ with the columns of the structure and form part of the structural frame of the grandstand. It is also feasible to construct precast raker beams as was done in the Corinthians Arena Sao Paolo, Brazil for the 2014 FIFA world cup.

precasting%2Bseaating%2Bunits
Double L precast seating units for stadium


Grandstand%2BDesign
Typical section through a grandstand

Precast seating decks are usually made of L-shaped reinforced concrete units of length between 7-8 meters spanning between the raker beams. The seating decks also rest on each other. The role of the third (resting support) is to stop the units from undergoing excessive twisting, and in general, provide extra stability. 

Seating units are used to span between raker beams and form the exposed surface to which the seats are bolted onto. The seating units are fabricated in moulds depending on the length of the span, angle of inclination/curve, and support conditions. The precast seating units can be easily installed on-site, and when the joints between units have been sealed, they form an effective barrier against external elements. They can also be easily installed in steel structures.

In a 2011 study at the University of Bath, human perception of vibration due to synchronised crowd loading was studied. Standard precast seating decks of 5.6 m length were used for the study. The precast seating decks used in the study were surpluses from a real premiership stadium project. The initial design length was 7.6 m but was cut to 5.6 m for the purpose of the study. The set up of the test rig is shown below.

browning stadium test rig model
Grandstand test set-up (Browning, 2011)

The precast seating deck used in the study was designed according to the requirements of BS 8110-1:1997 with a design live load of 4 kN/m2 for an assembly area with fixed seating. The live load was increased to 5 kN/m2 to allow for dynamic magnification (Browning, 2011). The model was observed to have an empty natural frequency of 6.47 Hz.

L shaped precast unit for stadium
Precast seating deck used in the study (Browning, 2011)

In a 2018 study in Romania, the serviceability of stadium seating decks under dynamic loading was evaluated. In the study, precast seating decks 150 mm thick with a total span of 9.28 m were used. The length of the horizontal flange was 990 mm while the vertical flange was 440 mm. Under the support conditions used in the study, a natural frequency of 6.75 Hz in the unloaded state was observed from the experiment. When numerically evaluated, a natural frequency of 6.76 Hz was observed for the unloaded structure and 4.75 Hz for the loaded structure.

The British design code BS 6399-1 sets the lower limit of the fundamental frequency for vertical vibrations of unloaded seating decks to 8.4 Hz, while the Green Guide (IStructE Dynamic performance for Permanent Grandstands subject to Crowd Action, 2008) set the same limit to 6 Hz but taking into account the weight of people on the structure. The authors concluded from the study that the section satisfied structural safety requirements, but human comfort due to vibration may be a major concern.

Design Example

Let us design a 6m long precast seating deck for a stadium with a section shown below;

section%2Bof%2Bterrace%2Bunit

fcu = 35 N/mm2; fyv = 460 N/mm2; fy = 460 N/mm2
Concrete cover = 30 mm
Unit weight of concrete = 24 kN/m3

Loading Analysis
Load type = uniformly distributed loading

Dead Load
Self weight of the unit = (24 × 0.15 × 0.25) + (24 × 0.15 × 0.95) = 4.32 kN/m
Make allowance for stair units, seats, and railings = 2 kN/m2

Live Load
For grandstands with fixed seating = 4 kN/m2
Making allowance for dynamic magnification qk = 5 kN/m2

At ultimate limit state;
n = 1.4gk + 1.6qk
n = 1.4(6.32) + 1.6(5) = 16.848 kN/m

loading

Design Moment Mmax @ 3.0m = (ql2)/8 = (16.848 × 62)/8 = 75.816 kN.m
End shears V = ql/2 = (16.848 × 6)/2= 50.544 kN

Design of the section (web) to resist the applied moment
M = 75.816 kN.m
Effective depth d = h – Cc – ∅⁄2 – ∅links

Assuming Y16mm for main bars and Y8mm for links
d = 400 – 30 – 10 – 8 = 352 mm

b = bw = 150mm (since the flange is at the tension zone)
k = M/fcubd2 = (75.816 × 106)/(35 × 150 × 3522) = 0.116
la = 0.5 + √[0.25- 0.116/0.9] = 0.848

ASreq = M/(0.95fy.la.d) = (75.816 × 106)/(0.95 × 460 × 0.848 × 352) = 581.22 mm2

In the web, provide 2Y16mm + 2Y12mm (ASprov = 628 mm2)
Provide 2Y12mm (Asprov = 226 mm2) in the compression zone (as hanger bars)

Spread the As,req also along the width of the tread
Provide Y12 @ 175mm c/c Top and Bottom (Asprov = 646 mm2/m)

Distribution bars
Provide Y10 @ 200mm c/c as closed links

Deflection Check
Basic span/effective depth ratio = 20 (for simply supported beams)

Modification factor for tension reinforcement
Service stress fs = (2fyAsreq)/(3Asprov) = (2 × 460 × 581)/(3 × 628)
fs = 283.715 N/mm2
m.f = 0.55 + (477 – fs) / 120(0.9 + M/bd2)
m.f = 0.55 + (477 – 283.715) / 120(0.9 + 4.079) = 0.873

Modification factor for compression reinforcement
1 + (100A’sprov/bd)/(3 + 100A’sprov/bd) = 1.124

Limiting span/effective depth = 0.873 × 1.124 × 20 = 19.625
Actual span/effective depth = 6000/352 = 17.045
Actual < Limiting, therefore deflection is okay

Design of the section to resist shear
Critical end shear V = 50.544 kN
Shear stress v = V/bd = (50.544 × 103) / (150 × 352) = 0.957 N/mm2

0.957 N/mm2 < 0.8 √35 < 5 N/mm2

Concrete resistance shear stress
vc = 0.632 × (100As/bd)1/3 × (400/d)1/4
vc =0.632 × [(100 × 628)/(150 × 352)]1/3 × (400/352)1/4
vc = 0.632 × 1.059 × 1.032 = 0.69 N/mm2

For concrete grades greater than 25 N/mm2
vc = vc(fcu/25)1/3 = 0.69 × (35/25)1/3 = 0.772 N/mm2

0.772 N/mm2 < 0.957 N/mm2
0.5 vc < v < (vc + 0.4)

provide minimum links with spacing
sv = (0.95AsvFyv)/0.4bv
(Trying 2 legs of Y8mm bar)
sv = (0.9 5 × 107 × 460)/(0.4 × 150) = 735.62mm

Maximum spacing of links = 0.75d
0.75 × 352 = 264m
Provide Y8 @ 250mm c/c links

Simplified dynamic consideration of the section
BS 6399 part 1: 1996 gave the following limit for the vertical frequency for structures subject to synchronized crowd loads = 8.4 Hz. IStructE Dynamic Performance for permanent Grand Stands (2008) gave the following limits;

3.5 Hz for viewing typical sporting events and classical concerts.
6 Hz for pop concerts and high-profile sporting events.
(3.5 Hƶ is given as the minimum vertical frequency acceptable for an empty grandstand).

The natural frequency for simply supported beams subjected to UDL (when the grandstand is empty, consider dead load only) is given by (considering the first mode of vibration);

fn = π/2[gEdIt/(wL4)]0.5 (See Salyards and Hanagan, 2005)

Where;
Ed = dynamic modulus of elasticity of the concrete.
It = Transformed moment of inertia
L = Span of section
g = acceleration due to gravity (m/s2)
w = Applied load (udl) = gk = 6.32 kN/m

An empirical relationship for concrete’s elastic modulus and dynamic modulus is given below;

Ec = 1.25Ed – 19 (BS 8110-2)

Where both units of Ec and Ed are in kN/mm2

Ec,28 = 20 + 0.2fcu = 20 + 0.2(35) = 27 kN/mm2

This expression does not apply for lightweight concretes or concrete that contains more than 500 kg/m3 of cement.
Hence, Ec = 1.25Ed – 19
27 kN/mm2 = 1.25Ed – 19
Ed = 46/1.25 = 36.8 kN/mm2

Ed = 3.68 x 107 kN/m2
EdIt = 3.68 x 107 x 1.65 x 10–3 = 60720 kN/m2
To account for a cracked section, let us say EdIt = 0.75 x 60720 = 45540 kN/m2

Therefore the natural frequency;
fn = π⁄2 [(9.81 × 45540)/(6.32 × 64)]0.5 = 11.6 Hz

This satisfies the IStructE and BS 6399 requirements for empty grandstands. The natural frequency should also be calculated for the whole structure (3D frame) and compared with the natural frequency of the precast units. However, Salyards and Hanagan (2005) recommended that when the natural frequency of the individual seating units is way higher than the expected natural frequency of the entire structure, they could be neglected in the 3D modelling.

Detailing Sketches

section%2Bdetailing


Concealing of PVC pipes in RC Columns

In modern building construction, PVC pipes (plumbing works) on the surface of buildings is not always very desirable. In a country like Nigeria, PVC surface pipes deteriorate quickly due to weather conditions thereby leading to increased maintenance costs. On the other hand, they are usually not aesthetically pleasing.

surface%2Bpiping
Fig 2: Surface piping in a building


To solve this problem, architects normally provide ducts for MEP services (which is the best practice) during the design of a building. Another option that is normally considered is to conceal the pipes in walls or structural members.

Two things are actually involved;

(1) If it is an intentional design, or
(2) if it is an afterthought.

When it is part of the design, the structural engineer takes into account the effect of the pipes before producing working drawings. But when it is an afterthought, there is need to carry out checks and evaluate the effect of the plumbing work on the structural element before signing off.

pipe%2Bin%2Bwall
Fig 3: PVC pipe concealed in masonry wall

We have always seen situations in buildings where structural members are compromised in order to allow pipes and other services pass through. This should not be so because starting from the onset, we should realise that services are part of a building, and should be considered during the planning and design stage. The flow of services in a building should not be an afterthought.

Let us use this example below to highlight the effect of installing PVC pipes in reinforced concrete columns.

Example
What is the effect of passing a 75 mm diameter pipe longitudinally through an axially loaded short reinforced concrete column with the following data?

Size of column = 230 x 230 mm
Grade of concrete = 25 Mpa
Grade  of steel = 410 Mpa
Reinforcement provided = 4Y16
Design axial load on column = 593 kN


Solution

From equation (39) of BS 8110-1:1997;

N = 0.35fcuAc + 0.7fyAsc

From the data provided above;
Asc = 804 mm2 (4Y16)
A=  (230 x 230) – 804 = 52096 mm2
N = [(0.35 × 25 × 52096) + (0.7 × 410 × 804)] = 686588 N = 686.588 kN

686.588 kN > 593 kN (Therefore column is adequate without the pipe)

On introducing the 75mm PVC pipe;
Area of pipe = (π × d2)/4 = (π × 752)/4 = 4417.86 mm2

Hence;
A=  (230 × 230) – 804 – 4417.86 = 47678.14 mm2
N = [(0.35 × 25 × 47678.14) + (0.7 × 410 × 804)] = 647931.725 N = 647.931 kN
647.931 kN > 593 kN (Therefore column is still adequate with the 75 mm pipe passing through it)

However, we should anticipate more complex interaction and verifications when the loading of the column is complex. Apart from the reduction in load carrying capacity of columns, care should be taken to ensure that the concrete is well consolidated to avoid honeycombs especially around the pipes. Also adequate care should be taken to ensure that the pipes are not leaking (inclusive of the joints) by pressure testing before concreting is done. Leakage of pipes might compromise the reinforcements by corrosion.

Summarily, adequate design and planning for pipe network in a building is the best solution – all options available should be evaluated. As far as possible, it is best to let the structural members be.

Question of the Day (25/06/2018)

Structville daily questions
From now henceforth, Structville will be publishing daily questions on different aspects of civil engineering. You are expected to enter your response in the comment section. At the end of every week, exceptional participants will stand a chance to win some gifts. This exercise is open to participants all over the world.

Today’s Question
What is the degree of static indeterminacy of the frame shown above?

Thank you for participating in exercise today, remember to enter your answer in the comment section. The main aim of this exercise to stimulate knowledge of structural analysis on the internet in a fun and exciting way. We are always happy to hear from you, so kindly let us know how you feel about Structville.

E-mail: info@structville.com
WhatsApp: +2347053638996

You can also visit Structville Research for downloads of civil engineering materials.

STRUCTVILLE REINFORCED CONCRETE DESIGN MANUAL
We have this very affordable design manual available…

final%2Bfront%2Bcover

Do you want to preview the book, click PREVIEW
To download full textbook, click HERE

Basic Information on Fire Protection of Buildings

Fire outbreak is a problem in buildings since it causes loss of human lives, injuries, destruction of properties, and poses serious environmental challenges. Injury and loss of life are caused by heat, inhalation of toxic gases generated by combustion of furnishings/properties, falling debris, etc. Destruction of property and structural damage and failure are caused by heat and burning of combustible material.


Prevention and control of damage due to fire can be achieved through the following means;

(1) Early detection by smoke and heat detectors or manual sighting followed by extinction of the fire by automatic sprinklers, manual application of water, foams, fire extinguishers etc.

Fire%2Bsprinkler%2Bsystem
Fig 2: Fire Sprinkler System

(2) Containment of the fire by dividing the building into fireproof compartments to prevent fire spread and smoke travels, and provision of fireproof escape routes, fire rated doors and windows, fire rated finishes, etc.

Fire%2Brated%2Bdoors
Fig 3: Fire rated doors

(3) Fire protection of load bearing structural members to ensure collapse does not occur before people can escape or the fire be extinguished. This is usually achieved by giving the building a fire rating during the design process.

structural steel beam column spray 2
Fig 4: Beams and Columns Protected By Spraying

The last two control methods form an essential part of the design considerations for steel structures (architectural and structural). All multi-storey commercial and residential buildings require fire protection of structural members, but single-storey and some other industrial buildings might not need protection.


Fire resistance requirements of buildings are usually based on the parameters influencing fire growth and development. These include:

  • Fire [probability of Fire occurrence, Fire spread, Fire duration, Fire load, Severity of fire…]
  • Ventilation conditions
  • Fire compartment (type, size, geometry)
  • Type of the structural element
  • Evacuation conditions
  • Safety of the rescue teams
  • Risk for the neighbouring buildings
  • Active fire fighting measures

Structural Considerations in Fire Design
Structural steelworks lose their strength on exposure to fire. Temperatures commonly reach 1200°C at the seat of the fire, while the critical temperature for steel is about 550°C. (see brief calculation below). At this temperature the yield stress of steel has fallen to about 0.7 of its value at ambient temperatures that is to the stress level in steel at working loads.

calculation

For instance in the calculation above, the critical temperature (failure temperature) is found to be 603°C (calculation according to EC3). The next step in the calculation is to determine the time at which the bare section reaches the critical temperature. This can offer the right information about the type of protection needed.

To request for a fully solved example of fire design (PDF) in a building, contact the author by clicking HERE.

Types of Fire Protection for Steel Structures

  • Solid protection for columns, where the concrete assists in carrying the load (this is not so much used in modern construction). Beams can also be cased in concrete. A concrete thickness of 50 mm will give about 2 hours protection.
  • Brick-clad steel-framed buildings, where brick provides the walling and fire protection, are a popular building system.
  • Hollow casing can be applied in the form of pre-fabricated casing units or vermiculite gypsum plaster placed on metal lathing.
  • Profile casing, where vermiculite cement is sprayed on to the surface of the steel member, is the best system to use for large plate and lattice girders and is the cheapest protection method. A thickness of 38 mm of cement lime plaster will give about 2 hours protection.
  • Intumescent coatings inflate into foam under the action of heat to form the protective layer.
  • Fire resistant ceilings are used to protect floor steel.
Thank you for visiting Structville today, and God bless you.


Punching Shear in Flat Slabs: A Design Example to Eurocode 2

Punching shear failure occurs in a slab when the magnitude of a concentrated load (such as that from a column) exceeds the shear strength or resistance of the slab or the column punches through the slab. The failure plane is located at a certain distance from the perimeter of the column and has a funnel-shaped failure pattern. The design for punching shear resistance in flat slabs normally involves controlling the thickness of the slab or providing punching shear reinforcement.

Generically, punching is a three-dimensional, brittle failure mechanism leading to a truncated cone that separates from the slab. The shear crack develops from tangential flexural cracks and propagates into the direction of the compression zone near the column edge constricting the circumferential compression ring with increasing loads. Once the punching shear resistance is reached the shear crack intersects the uncracked compression ring leading to a sudden penetration of the column into the slab.

punching shear failure pattern
Typical failure pattern for punching shear

The recommendations found in BS EN 1992 (Eurocode 2) are usually followed when designing punched shear reinforcement. To assess whether punched shear reinforcement is necessary, the shear stress in the concrete is computed at the column face and at the fundamental control perimeter u1 (2d from the column face).

The position of the outside control perimeter where shear reinforcement is no longer needed (uout) is then determined if reinforcement is necessary. Shear studs are placed starting at 0.3d or 0.5d from the column face to within 1.5d of the outer control perimeter (uout), with intermediate studs spaced at 0.75d intervals.

The most cost-effective approach will often be a radial arrangement, with rails spaced either 30° or 45° apart. To meet this requirement, extra secondary rails are installed as necessary. The tangential spacing between studs is kept to within 1.5d for studs inside the basic control perimeter (u1) and 2d for studs outside the basic control perimeter.

The suggested values from BS EN 1992 can be used to design shear load VEd for internal, edge, and corner columns where lateral stability does not depend on frame action between slabs and columns and where neighbouring spans differ by less than 25%.

Design for punching shear should take moment transfer into account at the intersection of the column and slab. The design punching shear can be obtained for structures whose lateral stability is not dependent on the frame action between the slab and columns and where adjacent spans do not differ in length by more than 25% by increasing VEd by 1.15 for internal columns, 1.4 for edge columns, and 1.5 for corner columns.

image 7

Generally, the following checks should be carried out: 

  • Ensure that maximum punching shear stress is not exceeded, i.e. vEd < vRd,max at the column perimeter
  • Determine whether punching shear reinforcement is required, i.e. whether vEd > vRd,c at the basic perimeter, u1
  • Determine whether punching shear reinforcement is required, i.e. whether vEd > vRd,c at at successive perimeters to establish uout    = the length of the perimeter where vEd = vRd,c. Perimeters within 1.5 d from uout need to be reinforced.

Where required provide reinforcement such that vEd ≤ vRd,cs.

where

vEd  =    applied shear stress. The shear force used in the verification should be the effective force taking into account any bending moment transferred into the slab (see above)

vRd,max = design value of the maximum punching shear resistance, expressed as a stress
vRd,c = design value of punching shear resistance of a slab without punching shear reinforcement, expressed as a stress
vRd,cs    = design value of punching shear resistance of a slab with punching shear reinforcement, expressed as a stress.

vRd,cs = 0.75 vRd,c + 1.5 (d/sr)Asw fywd,ef (1/u1d)sin a

where:

Asw = area of shear reinforcement in one perimeter around the column (subject to Asw,min)
sr    = radial spacing of perimeters of shear reinforcement
fywd,ef = effective design strength of reinforcement (250 + 0.25d) ≤ fywd
d    = mean effective depth in the two orthogonal directions (in mm)
u1   = basic control perimeter at 2from the loaded area
sin a = 1.0 for vertical shear reinforcement

Where required each perimeter should have
Asw = (vEd – 0.75 vRd,c)sr u1/(1.5 fywd,ef)

The punching shear resistance of a slab should be assessed for the basic control section (see Figure 6.12). The design punching shear resistance [MPa] may be calculated as follows:

vRd,c = CRd,c k (100 ρl fck)1/3 + k1 σcp   ≥ (vmin + k1 σcp)

where:
fck is the characteristic compressive strength of concrete, see Table 3.1
k= 1 + √200/d   ≤ 2.0
where d is the effective depth, in [mm]ρl= (ρlyρlz)1/2 ≤ 2%
ρlyρlz are longitudinal reinforcement ratios in y- and z- directions respectively. Their values should be calculated as mean values taking into account a slab width equal to column width plus 3d each side σcp= (σcy + σcz)/2,
where σcyσcz are the normal concrete stresses in the critical section in y- and z- directions (in [MPa], positive if compression):
σcy = NEd,y / Acy and σcy = NEd,z / Acz
NEd,yNEd,y are the longitudinal forces across the full bay for internal columns and the longitudinal force across the control section for edge columns. The force may be from a load or prestressing action.
AcyAcz are the areas of concrete according to the definition of NEd,yNEd,y respectively
CRd,c is a Nationally Determined Parameter, see § 6.4.4 (1)
vminis a Nationally Determined Parameter, see § 6.4.4 (1), or (6.3N) for the calculation of vmin following the Eurocode recommendation
k1 is a Nationally Determined Parameter, see § 6.4.4 (1).

Punching Shear Design Example

For the flat slab with the general arrangement as shown below, let us design the punching shear for column B1 given the following design information;

Ultimate axial force on column VEd = 400 kN
Thickness of slab = 250 mm
Dimension of column = 450 x 230 mm
Reinforcement of slab in the longer direction = H16@150mm (As,prov = 1340 mm2)
Reinforcement of slab in the shorter direction = H16@175mm (As,prov = 1149 mm2)
Grade of concrete = C30
Yield strength of reinforcement = 500 Mpa
Concrete cover to slab = 25mm

column%2Bstrips

Solution

Effective depth of slab in y-direction dy = 250 – 25 – (16/2) = 217 mm
Effective depth of slab in x-direction dx = 250 – 25 – 16 = 209 mm

ρly = (1340) / (1000 × 217) = 0.00617 (reinforcement ratio)
ρlx = (1149) / (1000 × 209) = 0.00549 (reinforcement ratio)

(a) Check shear at the perimeter of the column

VEd = β VEd/(u0d) < VRd,max

punching%2Blocations

From figure 6.21N of EN 1992-1-1;
β = 1.40
d = (217 + 209)/2 = 213 mm

u0 = c2 + 3d < c2 + 2c1 For edge columns (clause 6.4.5(3))

PUNCHING%2BAGAIN

u0 = 230 + (3 × 213) <  (230 + 2 × 450)
u0 = 869 mm
VEd = 1.40 × 400 × 1000/(869 × 213) = 3.025 MPa
VRd,max = 0.5 ν fcd
= 0.5 × 0.6(1 – fck/250) × αcc fckm
= 0.5 × 0.6(1 – 30/250) × 1.0 × (30 /1.5) = 5.28 MPa
VEd < VRd,max …OK


(b) Check shear at u1, the basic control perimeter
VEd = β VEd/(u1d) < VRd,c

β,VEd as before
u1 = c2 + 2c1 + π × 2d
u= 230 + (2 × 450) + (π × 2 × 213) = 2468 mm

VEd = 1.4 × 400 × 1000/(2468 × 213) = 1.065 MPa
VRd,c = 0.12 k(100 ρl fck)1/3

k = 1 + (200/d)1/2 = 1 + (200/213)1/2 = 1.969

ρl = (ρlyρlx)1/2 = (0.00617 × 0.00549)1/2 = 0.00582

VRd,c = 0.12 × 1.969(100 × 0.00582 × 30)1/3 = 0.613 MPa

VEd > VRd,c ?
1.065 MPa > 0.613 MPa … Therefore punching shear reinforcement required

NA check:
VEd ≤ 2.0VRd,c at basic control perimeter
1.06 MPa ≤ 2 × 0.613 MPa = 1.226 MPa – OK

(c) Perimeter at which punching shear no longer required
uout = β VEd/(dVRd,c)
= 1.4 × 400 × 1000/(213 × 0.613) = 4289 mm

Rearrange: uout = c2 + 2c1 + π rout
rout = (uout – (c2 + 2c1))/π
rout = (4289 – 1130)/π = 1005 mm

Position of outer perimeter of reinforcement from column face:
r = 1005 – 1.5 × 213 = 686 mm

Maximum radial spacing of reinforcement:
sr,max = 0.75 × 213 = 159.75 mm, say 150 mm

(d) Area of reinforcement
Asw ≥ (VEd – 0.75VRd,c)sru1/(1.5fywd,ef)
fywd,ef = (250 + 0.25d) = 303 MPa

Asw ≥ (1.065  – 0.75 × 0.613) × 150 × 2468/(1.5 × 303)
≥ 492 mm2 per perimeter

Provide 7H10 (Asprov = 549 mm2 per perimeter)

Within the u1 perimeter the link spacing around a perimeter,
st ≤ 1.5d = 1.5 × 213 = 319.5 mm

Outside the u1 perimeter the link spacing around a perimeter,
st ≤ 2d = 426 mm
Use say st,max = 300 mm

Minimum area of a link leg:
Asw,min ≥ [0.053 sr st sqrt(fck)] /fyk = (0.053 ×  150 ×  300 ×  √30) / 500
≥ 26 mm2

Use H10s (78.5 mm2) and 7 per perimeter.
@ 300 mm tangential spacing and @150 mm radial spacing

arrangement od punching shear reinforcement

Thank you for visiting Structville today and God bless you.


Design of Longitudinal Reinforcement in Piles

Precast piles are designed to withstand stresses caused during their installation, and the load from their service life. Bored piles on the other hand and usually designed to withstand the stresses they are subjected to while supporting the superstructure and other actions as may be anticipated. These could be earthquake forces, other lateral loads, or uplift forces.

Furthermore, piles of all types may be subjected to bending stresses caused by eccentric loading, either as a designed loading condition or as a result of the pile heads deviating from their intended positions. This post is aimed at exploring the methods of providing longitudinal reinforcement for bored piles, and the minimum reinforcement acceptable.

Buckling of piles that are embedded in a firm soil cannot occur unless they are loaded beyond their capacity, hence there is no need to design such piles as slender columns. However, when the piles are projecting above the ground level, then there is a need to consider such behaviour.

Also, when a pile passes through a very weak stratum of clay with low lateral stiffness, and is founded on a hard stratum, then buckling becomes a problem. If the undrained shear strength of the soil cu is less than 10 kN/m2, then there is a need to check for buckling.

Read Also….

Structural design of pile caps using strut and tie model
Design of piles in sand: Case Study of Lekki Pennisula Lagos

Reinforcement Requirement and Detailing of Bored Piles
Section 9.8.5 of EN 1992-1-1:2004 deals with the detailing requirements of bored piles. Clause 9.8.5(3) said that bored piles with a diameter not exceeding 600mm should be provided with a minimum longitudinal reinforcement of As,bpmin. The recommended minimum longitudinal reinforcement of cast-in-place bored piles is given in Table 9.6N of EN 1992-1-1:2004 and reproduced below;

Minimum%2Blongitudinal%2Breinforcement%2Bof%2Bbore%2Bpiles

The requirement further states that the minimum diameter for the longitudinal bars should not be less than 16 mm. Piles should have at least 6 longitudinal bars and the clear distance between bars should not exceed 200 mm measured along the periphery of the pile.

However, these rules differ from the requirements of BS EN 1536:2010 + A1(2015) which states that for reinforced piles, the minimum longitudinal reinforcement shall be 4 bars of 12 mm diameter, and the spacing should be maximised to allow proper flow of concrete but should not exceed 400 mm.

pile%2Breinforcement

According to clause 6.9.2.1 of BS 8004:2015, the design compressive resistance (Rc,d) of the reinforced length of a cast-in-place pile is given by;

Rc,d = fcdAc,d + fydAs,d

Where;
fcd = design compressive strength of the concrete = (αcc × fck)/(kf × γc)
αcc = factor taking into account the long-term reduction in strength of concrete (take as 0.85)
fck =  characteristic compressive strength of concrete
kf = A multiplier to the partial factor of concrete for concrete piles cast-in-place without permanent casing (value is 1.1)
γc = partial factor for concrete
Ac,d = cross-sectional area of pile

fyd = design yield strength of steel = (fyk / γs)
fyk =  characteristic yield strength of steel
γc = partial factor for steel
As,d = Area of steel required

The links, hoops, or helical reinforcements are required to be designed in accordance with EC2, but the diameter of the bar should not be less than 6 mm, or one-quarter of the maximum diameter of the longitudinal bars. The maximum reinforcement should be taken as 4% of the cross-sectional area.

According to clause 6.9.2.6, of BS 8004:2015, depending on the magnitude of loading, a cast-in-situ pile may be reinforced over its whole length, over part of its length, or merely provided with short splice bars at the top for bonding into the pile cap. If the concrete pile is expected to resist tensile forces, the reinforcement should be extended down to the full length.

Solved Example

A 500 mm diameter pile has a safe working load of 540 kN and the actual load it is being subjected to is 485 kN. Provide suitable reinforcement for the pile if it is a frictional pile embedded in dense sand and the characteristic strength of concrete and steel are 30 MPa and 500 MPa respectively.

Solution

Rc,d = fcdAc,d + fydAs,d

Ac,d = πd2/4 = (π × 5002)/4 = 196349.54 mm2
fcd = (0.85 × 30)/(1.1 × 1.5) = 15.45 N/mm2
fyd =  (500 / 1.15) = 434.782 N/mm2
Rc,d = 540000 N

540000  = (196349.54 × 15.45) + 434.782 As,d
A little consideration will show that solving for As,d will give us a negative value, therefore provide minimum reinforcement

Since Ac < 0.5 m2;
As,bpmin = 0.005 × Ac,d = 0.005 × 196349.54 = 982 mm2
Provide 6H16mm (As,prov = 1206 mm2)

567

Following strictly the detailing requirements of EC 2, a clear distance of 200 mm has not been exceeded.

Provide H10mm @ 300mm pitch spiral links

Read Also;

How to Apply Load Model 1 on Highway Bridges

Analysis of Trusses Using Direct Stiffness Method

Minimum Concrete covers (clause 7.6.4 BS 8004:2015)
60mm for piles with diameter > 600mm
50mm for piles with diameter ≤ 600 mm

The cover can be increased to 75mm under special circumstances.

Thank you for visiting Structville Today… God bless you